this post was submitted on 09 Apr 2024
1657 points (96.0% liked)
Solarpunk
5497 readers
7 users here now
The space to discuss Solarpunk itself and Solarpunk related stuff that doesn't fit elsewhere.
Join our chat: Movim or XMPP client.
founded 2 years ago
MODERATORS
you are viewing a single comment's thread
view the rest of the comments
view the rest of the comments
A chance for @bradorsomething, son of Gondor, to show his quality!
When we refer to the grounded conductor (the neutral), it does have a reference to the ground potential of the building receiving power. But the current generated by the power plant seeks the least resistive path back to its source, and the grounded conductor provides a path back to the generation plant that carries no voltage potential for electricity to draw towards or away from - the wire simply accepts the flow of energy to or from the power plant, to complete the circuit without changing the voltage potential.
There is also a grounding wire, which is green or bare, which is present in building in the US to allow anything electrified by stray wires to complete the circuit and trip the breakers in the panel. This wire joins to the grounded conductor (the white colored neutral) at the main panel where the utility provides power… utilities use the neutral as their ground, so current completes the circuit back to the power plant through the neutral.
When I say “the circuit looks for a path back to its source,” I’m playing a little fast and loose here… the current seeks the most potential to complete the circuit pathway. This path is almost always the return path to the power plant.
Join us next week, when I explain that lightning doesn’t care much about our wire at all, because at that scale it’s like the ocean caring about a moat at a sand castle!